MicroBulk Tank Derate Kit, 350 to 125 psig, Dual Relief Valve
Derate kit that lowers the relief setting of a 350 psig MAWP microbulk tank to 125 psig, for tanks that feed equipment with a 125 psig maximum inlet pressure, such as an automatic dewar filling station. The kit replaces the tank's single 350 psig primary relief valve with a pair of 125 psig relief valves on a common tee, which keeps relief capacity up at the lower set pressure. The tank's 525 psig rupture disc and nameplate MAWP stay as built.
- Primary relief: (2) brass 125 psig relief valves, 1/2" MNPT
- Manifold: 1/2" NPT stainless tee on a 1/2" brass hex nipple, threads into the existing 1/2" FNPT relief port
- Secondary relief: existing 525 psig rupture disc retained
- Regulator set points after derate: pressure building 95 psig, economizer 110 psig
Vent the tank to zero pressure before installation, and confirm the required relief capacity for the vessel.
JoyCan Part Number:
6269534
Specifications
| Part Type | Kit |
| Pressure | 125 psi |